ippc-ann-5-6-8-dir-2010-75

IPPC, Annexes V, VI, VIII - Provisions relating to industrial plants

This database contains emission limit values for polluting substances in waste gases and waste water, assigned according to facility type (i.e., combustion plants (Annex V), waste incineration/co-incineration plants (Annex VI), and installations producing titanium dioxide (Annex VIII)), under Directive 2010/75/EU on Industrial Emissions (Integrated Pollution Prevention and Control - IPPC).

Dust

EC / List no: - CAS no: -
Annex
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
Emission Limit
20 mg/nm3
fuel
Biomass and Peat
Fuel class
Solid or Liquid
Industrial plant
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
Part
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
Point
7
Thermal input
> 300
Notes
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines

37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU


Categories Display