ippc-ann-5-6-8-dir-2010-75

IPPC, Annexes V, VI, VIII - Provisions relating to industrial plants

This database contains emission limit values for polluting substances in waste gases and waste water, assigned according to facility type (i.e., combustion plants (Annex V), waste incineration/co-incineration plants (Annex VI), and installations producing titanium dioxide (Annex VIII)), under Directive 2010/75/EU on Industrial Emissions (Integrated Pollution Prevention and Control - IPPC).

Dust

EC / List no: - CAS no: -
Annex
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
Average period
Half-hourly (100 % of the measured values)
Average limit
30 mg/nm3
Industrial plant
Waste incineration plants
Part
Part 3 (VI) Air emission limit values for waste incineration plants
Point
1.2
Notes
21 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases.They are standardised at 11 % oxygen in waste gas except in case of incineration of mineral waste oil as defined in point 3 of Article 3 of Directive 2008/98/EC, when they are standardised at 3 % oxygen, and in the cases referred to in Point 2.7 of Part 6

39 For technical provisions regarding 'Monitoring of emissions' see Part 6 (Annex VI). For 'Formula to calculate the emission concentration at the standard percentage oxygen concentration' see Part 7 (Annex VI). For 'Assessment of compliance with emission limit values' see Part 8 (Annex VI) Directive 2010/75/EU