ippc-ann-5-6-8-dir-2010-75

IPPC, Annexes V, VI, VIII - Provisions relating to industrial plants

This database contains emission limit values for polluting substances in waste gases and waste water, assigned according to facility type (i.e., combustion plants (Annex V), waste incineration/co-incineration plants (Annex VI), and installations producing titanium dioxide (Annex VIII)), under Directive 2010/75/EU on Industrial Emissions (Integrated Pollution Prevention and Control - IPPC).

Dioxins and furans

EC / List no: - CAS no: -
Annex
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
Group
Dioxins and furans
Average period
A minimum of 6 hours and a maximum of 8 hours
Average limit
0.1 ng/nm3
Industrial plant
Cement kilns co-incinerating waste
Part
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
Point
2.2
Notes
25 'Dioxins and furans' means all polychlorinated dibenzo-p-dioxins and dibenzofurans listed in Part 2 of Annex VI. For the determination of the total concentration of dioxins and furans, the mass concentrations of the dibenzo-p-dioxins and dibenzofurans shall be multiplied by the equivalence factors before summing

28 All values are standardised at 10 % oxygen

30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases

35 Emission limit value defined as total emission limit for the total sum of dioxins and furans, expressed as average value over the sampling period

39 For technical provisions regarding 'Monitoring of emissions' see Part 6 (Annex VI). For 'Formula to calculate the emission concentration at the standard percentage oxygen concentration' see Part 7 (Annex VI). For 'Assessment of compliance with emission limit values' see Part 8 (Annex VI) Directive 2010/75/EU