legislation-obligation

Substance Regulatory Obligations

OBL

Nitrogen oxide (NOx)

EC number: -

CAS number: 11104-93-1

Last updated: 28/08/2021
ECHA Legislation Regulatory Obligations

Regulatory obligations may exist for this substance under the legislations under ECHA’s remit or for which ECHA has delegated tasks (i.e. REACH, CLP, BPR, PIC, CAD / CMD, WFD, and POPs). Please check the substance Infocard.

Industrial Emissions Directive

IPPC, Annexes V, VI, VIII - Provisions relating to industrial plants

This list contains emission limit values for polluting substances in waste gases and waste water, assigned according to facility type (i.e., combustion plants (Annex V), waste incineration/co-incineration plants (Annex VI), and installations producing titanium dioxide (Annex VIII)), under Directive 2010/75/EU on Industrial Emissions (Integrated Pollution Prevention and Control - IPPC). For this list, if a substance presents 2 values in the ''Average sampling duration'' field, these indicate minimum and maximum average sampling period.

Name CAS Expressed As Annex Group Average duration qualifier Average limit Maximum limit Average sampling duration Emission medium fuel Fuel class Part Point Thermal input Process/equipment Qualifier Notes  
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
300 mg/Nm3
Waste gases
Coal and lignite and other solid fuels, except pulverised lignite
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
450 mg/Nm3
Waste gases
Pulverised lignite
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
300 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
250 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
14 Combustion plants using solid fuels with a total rated thermal input greater than 500 MW, which were granted a permit before 1 July 1987 and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
450 mg/Nm3
Waste gases
Liquid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
12 Combustion plants in chemical installations using liquid production residues as non-commercial fuel for own consumption with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, shall be subject to an emission limit value for NOx of 450 mg/Nm3
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
15 Combustion plants using liquid fuels, with a total rated thermal input greater than 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 400 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Liquid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
01 The emission limit value is 450 mg/Nm3 for the firing of distillation and conversion residues from the refining of crude-oil for own consumption in combustion plants with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003
12 Combustion plants in chemical installations using liquid production residues as non-commercial fuel for own consumption with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, shall be subject to an emission limit value for NOx of 450 mg/Nm3
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
15 Combustion plants using liquid fuels, with a total rated thermal input greater than 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 400 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
150 mg/Nm3
Waste gases
Liquid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
01 The emission limit value is 450 mg/Nm3 for the firing of distillation and conversion residues from the refining of crude-oil for own consumption in combustion plants with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003
12 Combustion plants in chemical installations using liquid production residues as non-commercial fuel for own consumption with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, shall be subject to an emission limit value for NOx of 450 mg/Nm3
13 Combustion plants using solid or liquid fuels with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 Nov 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 Nov 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 450 mg/Nm3
15 Combustion plants using liquid fuels, with a total rated thermal input greater than 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, shall be subject to an emission limit value for NOx of 400 mg/Nm3
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
90 mg/Nm3
Waste gases
Light and middle distillates
Liquid
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
5
Gas turbines (including combined cycle gas turbines (CCGT))
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
100 mg/Nm3
Waste gases
Natural gas
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas fired combustion plants with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Blast furnace gas, coke oven gas or low calorific gases from gasification of refinery residues
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas fired combustion plants with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
03 300 mg/Nm3 for such combustion plants with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Gas other than natural gas, blast furnace gas, coke oven gas or low calorific gases from gasification of refinery residues
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas fired combustion plants with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
03 300 mg/Nm3 for such combustion plants with a total rated thermal input not exceeding 500 MW which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
50 mg/Nm3
Waste gases
Natural gas
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas turbines (including CCGT)
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
04 75 mg/Nm3 in the following cases, where the efficiency of the gas turbine is determined at ISO base load conditions: (i) gas turbines, used in combined heat and power systems having an overall efficiency greater than 75 %; (ii) gas turbines used in combined cycle plants having an annual average overall electrical efficiency greater than 55 %; (iii) gas turbines for mechanical drives
05 For single cycle gas turbines not falling into any of the categories mentioned under note (2), but having an efficiency greater than 35 % - determined at ISO base load conditions - the emission limit value for NO x shall be 50xɳ/35 where ɳ is the gas turbine efficiency at ISO base load conditions expressed as a percentage
06 Natural gas is naturally occurring methane with not more than 20 % (by volume) of inerts and other constituents
07 For gas turbines (including CCGT), the Nox and CO emission limit values set out in the table contained in this point apply only above 70 % load
08 For gas turbines (including CCGT) which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, the emission limit value for NOx is 150 mg/Nm3 when firing natural gas and 200 mg/Nm 3 when firing other gases or liquid fuels
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
120 mg/Nm3
Waste gases
Gases other than natural gas
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas turbines (including CCGT)
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
07 For gas turbines (including CCGT), the Nox and CO emission limit values set out in the table contained in this point apply only above 70 % load
08 For gas turbines (including CCGT) which were granted a permit before 27 November 2002 or the operators of which had submitted a complete application for a permit before that date, provided that the plant was put into operation no later than 27 November 2003, and which do not operate more than 1 500 operating hours per year as a rolling average over a period of 5 years, the emission limit value for NOx is 150 mg/Nm3 when firing natural gas and 200 mg/Nm 3 when firing other gases or liquid fuels
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
100 mg/Nm3
Waste gases
Gas
Part 1 (V) Emission limit values for combustion plants referred to in Article 30(2)
6
Gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
300 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
400 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
In case of pulverised lignite combustion
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
150 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Coal and lignite and other solid fuels
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
In case of pulverised lignite combustion
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
250 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
200 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
150 mg/Nm3
Waste gases
Biomass and Peat
Solid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
300 mg/Nm3
Waste gases
Liquid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
50-100
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
150 mg/Nm3
Waste gases
Liquid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
100-300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
100 mg/Nm3
Waste gases
Liquid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
4
> 300
Combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
50 mg/Nm3
Waste gases
Liquid
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
5
Gas turbines (including combined cycle gas turbines (CCGT))
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
100 mg/Nm3
Waste gases
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
6
Gas fired combustion plants with the exception of gas turbines and gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
50 mg/Nm3
Waste gases
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
6
Gas turbines (including combined cycle gas turbines (CCGT))
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
07 For gas turbines (including CCGT), the Nox and CO emission limit values set out in the table contained in this point apply only above 70 % load
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
V Annex V (Directive 2010/75/EU) Technical provisions relating to combustion plants
75 mg/Nm3
Waste gases
Part 2 (V) Emission limit values for combustion plants referred to in Article 30(3)
6
Gas engines
00 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correction for the water vapour content of the waste gases and at a standardised O2 content of 6 % for solid fuels, 3 % for combustion plants, other than gas turbines and gas engines using liquid and gaseous fuels and 15 % for gas turbines and gas engines
16 Gas turbines and gas engines for emergency use that operate less than 500 operating hours per year are not covered by the emission limit values set out in this point. The operator of such plants shall record the used operating hours
18 For single cycle gas turbines having an efficiency greater than 35 % - determined at ISO base load conditions - the emission limit value for NOx shall be 50xɳ/35 where ɳ is the gas turbine efficiency at ISO base load conditions expressed as a percentage
37 For technical provisions regarding 'Emission monitoring' see Part 3 (Annex V). For 'Assessment of compliance with emission limit values' see Part 4 (Annex V) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
500 mg/Nm3
1 d
Waste gases
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
2.2
Cement kilns co-incinerating waste
28 All values are standardised at 10 % oxygen
29 Until 1 January 2016, the competent authority may authorise exemptions from the limit value for NOx for Lepol kilns and long rotary kilns provided that the permit sets a total emission limit value for NO x of not more than 800 mg/Nm3
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
39 For technical provisions regarding 'Monitoring of emissions' see Part 6 (Annex VI). For 'Formula to calculate the emission concentration at the standard percentage oxygen concentration' see Part 7 (Annex VI). For 'Assessment of compliance with emission limit values' see Part 8 (Annex VI) Directive 2010/75/EU
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
300 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass and pulverised lignite
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
400 mg/Nm3
1 d
Waste gases
Pulverised lignite
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
300 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
250 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
400 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
150 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.1
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(2), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
300 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass and peat
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
250 mg/Nm3
1 d
Waste gases
Peat
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
150 mg/Nm3
1 d
Waste gases
Solid fuels with exception of biomass and pulverised lignite
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Pulverised lignite
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
250 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
200 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
150 mg/Nm3
1 d
Waste gases
Biomass
Solid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
31 O2 content 6%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
300 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
50-100
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
150 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
100-300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details
Nitrogen oxides (NOx)
11104-93-1
VI Annex VI (Directive 2010/75/EU) Technical provisions relating to waste incineration plants and waste co-incineration plants
100 mg/Nm3
1 d
Waste gases
Liquid
Part 4 (VI) Determination of air emission limit values for the co-incineration of waste
3.2.2
> 300
Combustion plants co-incinerating waste
For combustion plants referred to in Article 30(3), with the exception of gas turbines and gas engines
30 All emission limit values shall be calculated at a temperature of 273,15 K, a pressure of 101,3 kPa and after correcting for the water vapour content of the waste gases
32 O2 content 3%
Details