Endpoint:
flash point of flammable liquids
Type of information:
migrated information: read-across from supporting substance (structural analogue or surrogate)
Adequacy of study:
supporting study
Study period:
Between 05 April and 18 April 2012.
Reliability:
4 (not assignable)
Rationale for reliability incl. deficiencies:
other: Cited from ECHA disseminated dossier Query date: 2015-07-22 For justification of read across please refer to IUCLID section 13.

Data source

Reference
Reference Type:
other: ECHA disseminated dossier
Title:
No information
Report date:
2015

Materials and methods

Test guideline
Qualifier:
according to guideline
Guideline:
EU Method A.9 (Flash-Point)
Deviations:
no
GLP compliance:
yes
Type of method:
equilibrium method closed cup

Test material

Constituent 1
Reference substance name:
939-183-5
EC Number:
939-183-5
IUPAC Name:
939-183-5
Details on test material:
Identification: ERC#18
Description: clear colorless liquid
Batch: 9114460/002
Purity: 100 % (UVCB)
Expiry / Retest Date: 23 January 2013
Storage Conditions: room temperature in the dark

Results and discussion

Flash point
Flash point:
155 °C
Atm. press.:
99.6 kPa

Any other information on results incl. tables

Results

Results of the flash point determination are shown in the following table.

 

Table 1

 

Temperature (ºC)

Observations

18

No flash.

23

No flash.

28

No flash.

33

No flash.

38

No flash.

43

No flash.

48

No flash.

53

No flash.

58

No flash.

63

No flash.

68

No flash.

68 (fresh sample)

No flash.

73

No flash.

78

No flash.

83

No flash.

88

No flash.

93

No flash.

98

No flash.

103 (fresh sample)

No flash.

108

No flash.

113

No flash.

118

No flash.

123

No flash.

128

No flash.

133

No flash.

138

No flash.

143

No flash.

148

No flash.

153

No flash.

153 (fresh sample)

No flash.

158

A blue flash spread across the sample cup.

153 (fresh sample)

No flash.

154

No flash.

155

A blue flash spread across the sample cup.

155 (fresh sample)

A blue flash spread across the sample cup.

155 (fresh sample)

A blue flash spread across the sample cup.

 

Atmospheric pressure =         99.6 kPa
Corrected flash point =         155.397 ºC

 

Applicant's summary and conclusion

Conclusions:
The flash point of the test item has been determined to be 155 ±2 °C.
Executive summary:

Test System The determination was carried out using a closed cup flash point tester , using a procedure designed to be compatible with Method A9 Flash Point of Commission Regulation (EC) No 440/2008 of 30 May 2008.

An aliquot (2 mL for temperatures up to 100 ºC and 4 mL for temperatures above 100 ºC) of the test item was injected into the sample cup of the Setaflash 30000-0 tester. The sample was heated and allowed to equilibrate at the set temperature. The test flame was introduced into the sample cup for approximately 2½ seconds by sliding the cup shutter open. Observations were made for ignition of the vapor. If no ignition occurred, the temperature was increased and the test flame re-introduced. This was repeated until the lowest reproducible temperature at which a flash occurred, using a fresh sample, was determined.

The flash point of the test item has been determined to be 155 ±2 °C.